Steel Tanks

Application
Above ground and underground tanks with double and single wall option to AdBlue storage with anticorrosion protection EMAPUR (for aboveground) or ENDOPREN (for underground), fully pre-piped and equipped. Special epoxy lined inner tank for ultimate protection of AdBlue.
Equipment
- Inspection shaft DN 600 with gasket
- Inspection shaft flange
- Tank piping:
- Vent socket DN 50
- Leak detection system sockets
- Manual level control sockets
- Socket for Petro-Vend ???
- Filling pipe with overfilling limiter LAFON
- Drainage pipe
- Leaking detection system Afriso type LAG 14 ER
- Liquid detection fluid
Product advantages
- Market leader in high-quality steel lined tanks
- Custom designed and fitted for each individual user
- Structurally guaranteed for 20 years against defect
- Most ‘invisible' and durable solution to AdBlue storage
- Competitively priced – multi installation special terms available.
»Above ground tank (container fuel station)
Technical data and product reliability
- Steel, situated on the ground, double-skinned, manufactured according to DIN 6616
- Basic material: S235JRG2 according to EN 10025
- Pressure tested for tightness: inner skin – 0.1 MPa, outer skin – 0.06 MPa
- Technical documentation approved by the Technical Inspection Office and the Head Office of Measures.
- The tank is coated with anticorrosive polyurethane Emapur coat in any colours according to RAL table.
- Leakage control system
- Safety railing, ladder, service platform – galvanised steel
- Fuel loading installation: The tank is fitted with DN 80 filling pipe with a French SOLO overfilling protection valve and hydraulic closure. The cistern drain pipe is connected to DN 80 DC-3 type fast connector located on the tank manhole.
- Support on documentation, Tank attestation and foundation on request
»Underground tank (double wall)
- Technical data and product reliability
- Manufactured in line with DIN 6608-2 or EN 12285
- Basic material: S235JRG2 according to EN 10025
- Tightness under pressure tested: inner skin 0.2 MPa or 0.075 MPa, outer skin 0.06 MPa or 0.04 MPa (depending on the tank class)
- External coat – Polyurethane ENDOPREN coat resistant to puncture 1400 V
|